Quantcast

Wire Lay Factor for Layer-Wound Coils

Last modified by
on
Jan 28, 2025, 6:22:26 PM
Created by
on
Apr 6, 2018, 2:47:49 PM

This Winding Lay Factor dataset contains a lookup table for the lay factor, a measure of density of windings in a winding build of a transformer.  This Winding Lay Factor is used in the calculation of the Transformer Window Utilization `K_u`.


Entered
By
AWG
Insulated_Wire_OD_Min(cm)
Insulated_Wire_OD_Max(cm)
Wire Lay Factor
2018-04-06 22:05:54
eng
10 to 25
0.267
0.0505
0.9
2018-04-06 21:29:24
eng
26 to 30
0.0452
0.0294
0.89
2018-04-06 21:28:15
eng
31 to 35
0.0267
0.017
0.88
2018-04-06 21:27:29
eng
36 to 38
0.0152
0
0.87
2018-04-06 21:26:34
eng
39 to 40
0.0109
0.0096
0.86
2018-04-06 21:25:49
eng
41 to 44
0.00863
0
0.8